Hydraulics and pipes
Manning's Equation Pipe Flow Calculator
Manning's equation is used to size storm sewers, culvert barrels and sanitary sewers flowing by gravity. Enter the pipe diameter, slope and Manning's n to get the full-flow capacity and velocity.
Formula
Manning's equation in US customary units: Q = (1.49/n) × A × R^(2/3) × S^(1/2), with Q in cfs, A in ft², R = A/P in ft and S in ft/ft. For a full circular pipe A = πD²/4 and R = D/4. Velocity V = Q/A.
Worked example
An 18 in concrete pipe (n = 0.013) at 0.5% slope: A = 1.767 ft², R = 0.375 ft, R^(2/3) = 0.520, √0.005 = 0.0707. Q = (1.49 ÷ 0.013) × 1.767 × 0.520 × 0.0707 = 7.45 cfs. V = 7.45 ÷ 1.767 = 4.21 ft/s.
Assumptions and limits
- Steady, uniform gravity flow with the pipe just full (no surcharge).
- Partly full pipes carry less (except around 93% depth, where flow slightly exceeds full-flow capacity).
- Typical n values: 0.012 to 0.013 concrete and smooth plastic, 0.024 corrugated metal.
Frequently asked questions
What Manning's n should I use?
FHWA HDS-5 and HEC-22 list about 0.012 to 0.013 for concrete pipe, 0.009 to 0.015 for smooth-wall plastic depending on condition, and about 0.022 to 0.027 for 2-2/3 in by 1/2 in corrugated metal. Local agencies often specify design values.
What is the minimum velocity for a sewer?
Sanitary sewers are commonly designed for at least 2 ft/s when flowing full so solids do not settle (Ten States Standards). Storm drains commonly target at least 2.5 to 3 ft/s.
Why is 1.49 in the equation?
It converts the SI form (coefficient 1.0) to US customary units: 1.49 is approximately the cube root of 3.2808 (feet per meter), 3.2808^(1/3) = 1.486.
Sources
- FHWA HEC-22, Urban Drainage Design Manual, 3rd Edition, Chapter 6
- FHWA HDS-5, Hydraulic Design of Highway Culverts, 3rd Edition (2012), Appendix C Manning's n values
- Recommended Standards for Wastewater Facilities (Ten States Standards), 2014 Edition, Section 33