Hydraulics and pipes

Hazen-Williams Head Loss Calculator

The Hazen-Williams equation is the standard method for friction loss in water distribution and fire sprinkler piping. Enter flow in gpm, inside diameter in inches, pipe length and the C factor.

Friction head loss  ft
Pressure loss  psi
Velocity  ft/s

Formula

US form: hf (ft) = 10.44 × L × Q^1.852 ÷ (C^1.852 × d^4.8655), with L in ft, Q in gpm and d in inches. Pressure loss (psi) = hf × 0.4335 for water at about 60 °F. Velocity (ft/s) = 0.4085 × Q ÷ d².

Worked example

100 gpm through 200 ft of 2 in Schedule 40 PVC (d = 2.067 in, C = 140): hf = 10.44 × 200 × 100^1.852 ÷ (140^1.852 × 2.067^4.8655) = 32.72 ft, or 14.18 psi (about 7.1 psi per 100 ft). Velocity = 0.4085 × 100 ÷ 2.067² = 9.56 ft/s, which is high; a 2.5 in line would cut the loss sharply.

Assumptions and limits

  • Water near room temperature in full, pressurized, turbulent flow.
  • Minor losses from fittings and valves are not included; add equivalent lengths.
  • Typical C values: 150 PVC and HDPE, 130 to 140 new ductile iron (lined), 100 older cast iron, 120 copper per NFPA 13.

Frequently asked questions

What C value should I use?

NFPA 13 lists 150 for plastic pipe, 140 for cement-lined ductile iron, 120 for black steel in wet systems and 150 for copper. Older unlined pipe in service may be 100 or less.

Hazen-Williams or Darcy-Weisbach?

Hazen-Williams is empirical and valid for water at ordinary temperatures. Darcy-Weisbach works for any fluid and is more accurate outside that range.

Is a velocity of 9.6 ft/s too high?

Many designers keep water service and distribution velocities below about 5 to 8 ft/s to limit noise, pressure loss and water hammer.

Sources

  • AWWA Manual M32, Computer Modeling of Water Distribution Systems
  • NFPA 13, Standard for the Installation of Sprinkler Systems (2022), hydraulic calculation procedures (Hazen-Williams formula and C values)